On Saturday afternoon, 21 November 2026, a candy factory in the Pancatama Industrial Estate, Cikande, Serang Regency, Banten, caught fire. The Banten Police chief said 24 body bags had been recovered by the time the first day of searching was paused at 18.00 WIB on Sunday, 22 November 2026, with the search due to resume at 07.00 WIB on Monday (Ikhsanudin, 2026a). By 17.00 WIB the bags had reached the Banten Police Bhayangkara Hospital, where the Disaster Victim Identification (DVI) team uses DNA and fingerprint matching (Mufarida, 2026). The police chief said DNA testing is the only route to identification because the victims cannot be recognised physically, so the number of bags is not yet the number of deaths (Akhyar, 2026).
About 50 employees were reported as unaccounted for, a figure that may rise or fall because the fire coincided with a shift change (Ikhsanudin, 2026a). No official investigation report is available, and the police plan a forensic laboratory examination to establish the cause (Biro Administrasi Pimpinan Sekretariat Daerah Provinsi Banten [Biro Adpim Banten], 2026a). Our thoughts are with the families. We do not discuss the cause; we use the RSET and ASET escape time framework to show how a plant can check its alarms, exits and drills.
The First Two Days
Reports differ on when the fire started: around 16.00 WIB (CNN Indonesia, 2026), 16.30 WIB (Nugraha, 2026) or 17.00 WIB (CNBC Indonesia, 2026). Early reports said the fire hit the office building and warehouse before spreading to several warehouse areas (Nugraha, 2026). A second-shift worker on the ground floor said that at about 16.30 he heard someone shout that there was a fire, saw flames from the candy cooking section, and got out easily because his workroom was close to an exit. He said no siren sounded and that workers learned of the fire from colleagues in other sections. After he got out the power failed, and he did not know what conditions were like on the upper floor (kumparanNEWS, 2026). The authorities have not confirmed this account.
The company said the plant had proper evacuation routes, held regular evacuation drills with the fire service, and that its hydrants worked, but that the fire grew too large too quickly (Ikhsanudin, 2026b). Fifteen fire engines were deployed, and partial collapse and darkness kept crews from reaching the whole site overnight (Biro Adpim Banten, 2026a). The Banten search and rescue office said hot spots and collapsed material forced the search to be divided into sectors (Biro Adpim Banten, 2026b).
How many people were inside is also uncertain. In the early hours of 22 November, the Serang Regency disaster agency said the building held 59 people from two work teams, 16 of whom were safe (detikNews, 2026). A police post at one point listed 54 employees, 42 of them still being traced (Nugraha, 2026), and the company's human resources figure later rose from about 30 to about 50 (Akhyar, 2026). The Serang Police chief said matching attendance records was hampered because power had not been restored, and workers' phones had been in their lockers (Biro Adpim Banten, 2026b).
Computing RSET and ASET
Life safety in a fire can be judged by comparing two times. Available Safe Egress Time (ASET) runs from ignition until conditions at a location can no longer be tolerated because of smoke, heat or toxic gases. Required Safe Egress Time (RSET) is the time occupants need to escape: detection, plus warning, plus pre-movement, plus travel to a place of safety. An evacuation is judged safe when RSET is shorter than ASET by an adequate margin (Purser, 2003).
Purser (2003) stresses that pre-movement time, the delay between receiving a cue and starting to move out, is often a larger part of RSET than walking time. It varies with occupancy, warning, occupants, building complexity and fire safety management. Kuligowski (2013) describes how people perceive cues, interpret the risk and then decide, and ambiguous cues stretch that process. Lovreglio et al. (2019) built a pre-evacuation database from 9 fires and 103 evacuation drills involving 13,591 people in 16 countries, grouped by occupancy, so that this delay can be modelled as a distribution rather than a single number.
In a plant the method has four steps. First, set credible fire scenarios for each area, warehouses and production included. Second, estimate when the alarm is actually heard in each area, not just when a detector operates. Third, estimate pre-movement time from your own timed drills. Fourth, trace the longest route out and compare it with how quickly conditions on that route would deteriorate.
Applying It to Cikande
Public information is not enough to compute RSET and ASET here, but the framework sorts out what investigators need to examine.
Detection and warning have drawn the most attention. Should the account of a silent siren be confirmed, warning would have depended on shouting and word of mouth, which in our assessment reaches each area at a different time and reaches areas far from the fire last. We do not know whether the plant had an automatic alarm or whether it sounded elsewhere. Indonesia's automatic fire alarm regulation, PER.02/MEN/1983, requires at least one alarm bell (Article 44), batteries able to keep the system signalling for at least 4 days without mains power (Article 39), and weekly, monthly and annual testing (Articles 57 to 60) (Departemen Tenaga Kerja [Depnaker], 1983). The reported power failure (kumparanNEWS, 2026) makes standby power a fair question.
Pre-movement was affected by the shift change. The police chief said some employees who should already have gone home were thought to be still inside (Ikhsanudin, 2026a). At shift change there are more people inside and it can be unclear who leads each area out. In our view this hour belongs in drill scenarios.
Travel time depends on a layout that has not been published. The account mentions at least a ground floor and a floor above (kumparanNEWS, 2026). Public Works Minister Regulation 26/PRT/M/2008 on fire protection in buildings counts travel distance to an exit all the way down to ground level (Departemen Pekerjaan Umum [DPU], 2008), so workers upstairs face a longer RSET than those beside a ground-floor door. The statement that the fire grew very fast (Ikhsanudin, 2026b) hints at a short ASET, but without data on materials and protection we cannot judge it.
One gap is already visible: accounting for people. The figures of 59, 54, about 40 and about 50 come from different sources at different times (detikNews, 2026; Nugraha, 2026; Biro Adpim Banten, 2026a; Akhyar, 2026). When attendance data needs electricity and workers carry no phones, responders cannot quickly confirm who is out, which in our view adds to the families' burden.
Lessons from Other Fires
The chicken processing plant fire in Hamlet, North Carolina, United States, on 3 September 1991 is widely taught. Of the 90 workers inside, 25 died and 54 were injured. Doors were padlocked against theft and flies, there was no fire alarm and no sprinklers, most survivors left through the unlocked main entrance, and three earlier fires had not led to the doors being unlocked (Fishwick, 2018). In Kosambi, Tangerang, in 2017, a review of the firecracker factory explosion recorded 47 deaths and named the absence of evacuation routes and exits as one reason for the high toll (Qadriina, 2024).
We cite both as pattern comparisons, not to equate their causes with Cikande. The shared pattern: the toll depends on how quickly people learn of the fire and how open the way out is.
What Cannot Be Concluded
The siren account comes from one person and is unconfirmed. Early reports and the worker's account place the start of the fire in different areas (Nugraha, 2026; kumparanNEWS, 2026). The floor plan, number of exits and alarm test records have not been released, and the death toll can only be confirmed once identification is complete. We therefore conclude no system failure and judge no individual.
Auditing the Way Out
These steps apply to any factory or warehouse, not specifically to Cikande. The legal starting point is Law 1 of 1970 on Work Safety, which sets work safety requirements to prevent, reduce and extinguish fires and to provide the opportunity or means to escape during a fire (Article 3(1)(b) and (d)) (Pemerintah Republik Indonesia, 1970).
- Count occupant load per floor, including when two shifts overlap. Each floor needs at least two means of egress, three where the load exceeds 500 and four where it exceeds 1,000 (DPU, 2008, clauses 3.12.1.1 and 3.12.1.2).
- Walk the route from the farthest point to outside the building. Measure travel distance, look for dead ends, and keep routes clear of goods and pallets (DPU, 2008, clauses 3.6 and 3.11).
- Check every exit door during working hours. Doors must open from the inside without a key, tool or special knowledge, and required fire doors serving a room with an occupant load of 50 or more must swing in the direction of travel (DPU, 2008, clauses 3.7.1.2 and 3.7.2.2). NFPA 101 applies the same principles to the number of exits, travel distance, locking, lighting and marking (National Fire Protection Association [NFPA], 2024). Ban the locking of exit doors while anyone is inside, whatever the reason.
- Test emergency lighting every 30 days for at least 30 seconds, and once a year for 1.5 hours on battery systems (DPU, 2008, clause 3.16.2.1).
- Test alarms as PER.02/MEN/1983 requires: a simulated sounding every week, a simulated fire every month, at least 20% of detectors every year, all recorded in the logbook (Depnaker, 1983). In noisy areas, make sure the signal is heard; NFPA 72 requires public mode audible signals at least 15 dB above the average ambient sound level (NFPA, 2025).
- Appoint fire wardens at a rate of at least 2 for every 25 workers, with duties that include directing evacuation, and keep a written fire emergency plan (Depnaker, 1999, Articles 2, 6 and 7).
- Hold regular timed drills, including unannounced ones and at shift change. Government Regulation 50 of 2012 on OHS management systems requires emergency procedures to be tested periodically and warning systems to be inspected, tested and maintained (Appendix I and Appendix II criterion 6.7.6) (Pemerintah Republik Indonesia, 2012). Record the time from alarm to the last person reaching the assembly point.
- Set up a head count that needs neither electricity nor phones, such as team lists per area that wardens carry to the assembly point.
A common belief needs correcting: that evacuation routes and hydrants make a plant safe. Through the RSET and ASET lens, time decides: how quickly everyone knows, how quickly they move, and whether every route stays open until the last person is out.
How Nusa Safety Helps
As an independent third party, the Nusa Safety team can help factories and warehouses test their evacuation readiness through a fire and emergency safety audit (FESA), which reviews alarms, the emergency plan, the warden organisation and evacuation performance. Nusa Safety also designs emergency preparedness drills that time the sequence from alarm to head count, runs fire warden and fire brigade training with licensed PJK3 partners, and carries out building and facility safety assessments.
Nusa Safety issues only internal training certificates, not competency certificates or OHS licences, and does not hold a PJK3 licence. Conversations can start through the contact page.
This article is general information and not legal or professional advice for any specific case.
References
- Akhyar, A. (2026, November 22). Polisi gunakan tes DNA untuk identifikasi korban kebakaran pabrik permen di Cikande [Police use DNA tests to identify victims of the Cikande candy factory fire]. VIVA.co.id. https://www.viva.co.id/berita/nasional/1945600-polisi-gunakan-tes-dna-untuk-identifikasi-korban-kebakaran-pabrik-permen-di-cikande
- Biro Administrasi Pimpinan Sekretariat Daerah Provinsi Banten. (2026a, November 21). Gubernur Banten Andra Soni pantau langsung penanganan kebakaran pabrik permen di Cikande [Banten Governor monitors the response to the Cikande candy factory fire]. https://biroadpim.bantenprov.go.id/berita/gubernur-banten-andra-soni-pantau-langsung-penanganan-kebakaran-pabrik-permen-di-cikande
- Biro Administrasi Pimpinan Sekretariat Daerah Provinsi Banten. (2026b, November 22). Dampingi keluarga korban kebakaran pabrik di Cikande, Gubernur Andra Soni pastikan evakuasi berjalan maksimal [Accompanying victims' families, the Governor ensures the evacuation is maximised]. https://biroadpim.bantenprov.go.id/berita/dampingi-keluarga-korban-kebakaran-pabrik-di-cikande-gubernur-andra-soni-pastikan-evakuasi-berjalan-maksimal
- CNBC Indonesia. (2026, November 22). Pabrik permen di Cikande terbakar, Basarnas cari 39 karyawan hilang [Candy factory in Cikande burns, Basarnas searches for 39 missing employees]. https://www.cnbcindonesia.com/news/20261122095030-4-787266/pabrik-permen-di-cikande-terbakar-basarnas-cari-39-karyawan-hilang
- CNN Indonesia. (2026, November 22). Update kebakaran pabrik permen Cikande: 7 kantong jenazah dievakuasi [Cikande candy factory fire update: 7 body bags recovered]. https://www.cnnindonesia.com/nasional/20261122151116-20-1430085/update-kebakaran-pabrik-permen-cikande-7-kantong-jenazah-dievakuasi
- Departemen Pekerjaan Umum. (2008). Peraturan Menteri Pekerjaan Umum Nomor 26/PRT/M/2008 tentang Persyaratan Teknis Sistem Proteksi Kebakaran pada Bangunan Gedung dan Lingkungan [Public Works Minister Regulation 26/PRT/M/2008 on technical requirements for fire protection systems in buildings and their surroundings]. https://peraturan.bpk.go.id/Details/104475
- Departemen Tenaga Kerja. (1983). Peraturan Menteri Tenaga Kerja Nomor PER.02/MEN/1983 tentang Instalasi Alarm Kebakaran Automatik [Manpower Minister Regulation PER.02/MEN/1983 on automatic fire alarm installations]. https://betterwork.org/wp-content/uploads/781-3-Per-02_MEN_1983-Tentang-Instalasi-Alarm-Kebakaran-Automatik.pdf
- Departemen Tenaga Kerja. (1999). Keputusan Menteri Tenaga Kerja Nomor KEP.186/MEN/1999 tentang Unit Penanggulangan Kebakaran di Tempat Kerja [Manpower Minister Decree KEP.186/MEN/1999 on workplace fire response units]. https://jdih.kemnaker.go.id/asset/data_puu/1999kmnaker186.pdf
- detikNews. (2026, November 22). BPBD Serang catat 16 karyawan selamat dalam kebakaran pabrik di Cikande [Serang disaster agency records 16 employees safe in the Cikande factory fire]. https://news.detik.com/berita/d-8764003/bpbd-serang-catat-16-karyawan-selamat-dalam-kebakaran-pabrik-di-cikande
- Fishwick, T. (2018). The Hamlet chicken processing plant fire: Outcomes and good practices for avoiding a recurrence. Loss Prevention Bulletin, 260, 6-10. https://www.icheme.org/media/1991/lpb260_pg06.pdf
- Ikhsanudin, A. (2026a, November 22). 24 kantong mayat dievakuasi dari pabrik permen terbakar di Serang [24 body bags recovered from the burned candy factory in Serang]. detikNews. https://news.detik.com/berita/d-8764799/24-kantong-mayat-dievakuasi-dari-pabrik-permen-terbakar-di-serang
- Ikhsanudin, A. (2026b, November 22). Perusahaan sebut pabrik permen terbakar di Serang penuhi standar keamanan [Company says the burned candy factory in Serang met safety standards]. detikNews. https://news.detik.com/berita/d-8764692/perusahaan-sebut-pabrik-permen-terbakar-di-serang-penuhi-standar-keamanan
- Kuligowski, E. D. (2013). Predicting human behavior during fires. Fire Technology, 49(1), 101-120. https://doi.org/10.1007/s10694-011-0245-6
- kumparanNEWS. (2026, November 22). Sirene tak berbunyi, pegawai cerita detik-detik kebakaran pabrik [...] di Serang [No siren sounded: an employee recounts the factory fire in Serang]. kumparan. https://kumparan.com/kumparannews/28ccjdZWJML
- Lovreglio, R., Kuligowski, E., Gwynne, S., & Boyce, K. (2019). A pre-evacuation database for use in egress simulations. Fire Safety Journal, 105, 107-128. https://doi.org/10.1016/j.firesaf.2018.12.009
- Mufarida, B. (2026, November 22). Kebakaran pabrik permen di Cikande: 24 kantong jenazah dibawa ke RS Bhayangkara [Cikande candy factory fire: 24 body bags taken to Bhayangkara Hospital]. Okezone. https://news.okezone.com/read/2026/11/22/340/3255582/kebakaran-pabrik-permen-di-cikande-24-kantong-jenazah-dibawa-ke-rs-bhayangkara
- National Fire Protection Association. (2024). NFPA 101: Life safety code (2024 ed.). https://www.nfpa.org/codes-and-standards/nfpa-101-standard-development/101
- National Fire Protection Association. (2025). NFPA 72: National fire alarm and signaling code (2025 ed.). https://www.nfpa.org/codes-and-standards/nfpa-72-standard-development/72
- Nugraha, B. (2026, November 22). Kebakaran pabrik di Cikande, enam kantong jenazah dievakuasi [Factory fire in Cikande, six body bags recovered]. VIVA.co.id. https://www.viva.co.id/berita/nasional/1945511-kebakaran-pabrik-di-cikande-enam-kantong-jenazah-dievakuasi
- Pemerintah Republik Indonesia. (1970). Undang-Undang Nomor 1 Tahun 1970 tentang Keselamatan Kerja [Law 1 of 1970 on Work Safety]. Lembaran Negara Republik Indonesia Tahun 1970 Nomor 1. https://jdih.kemnaker.go.id/peraturan/detail/49/undang-undang-nomor-1-tahun-1970
- Pemerintah Republik Indonesia. (2012). Peraturan Pemerintah Nomor 50 Tahun 2012 tentang Penerapan Sistem Manajemen Keselamatan dan Kesehatan Kerja [Government Regulation 50 of 2012 on the application of OHS management systems]. Lembaran Negara Republik Indonesia Tahun 2012 Nomor 100. https://jdih.kemnaker.go.id/peraturan/detail/58/peraturan-pemerintah-nomor-50-tahun-2012
- Purser, D. A. (2003). ASET and RSET: Addressing some issues in relation to occupant behaviour and tenability. Fire Safety Science, 7, 91-102. https://doi.org/10.3801/IAFSS.FSS.7-91
- Qadriina, H. I. (2024). Manajemen bencana industri pada kasus ledakan pabrik petasan Kosambi, Tangerang tahun 2017 [Industrial disaster management in the 2017 Kosambi, Tangerang firecracker factory explosion]. Human Error and Safety, 1(1). https://doi.org/10.61511/hes.v1i1.2024.534